Fire curtains are composed of two main elements:
-
Fluorocarbon fabric coated in grey fibreglass.
Maximum width = 5.96 m. Unrolled length = 6.00 m
-
Load-bearing structure (ROLLER CONTAINER) in prepainted galvanised steel
The curtains used for compartmentalisation as an alternative to traditional methods conform to EN 13501-2 standard Fire classification of construction products and building elements. Classification: E120 or EW60 or EI 60-C according to EN 13501-2.
- Maximum duration at temperature: 120 minutes standard curve
- Maximum irradiation: less than 15kW/m2 for 90 minutes in accordance with EN 1634-1.
- Maximum insulation: 60 minutes with closing capacity for 60 minutes Material: silicone fabric with intumescent foam in a thickness of 13 mm
The curtains conform to the EN 16034 standard 